Installation

2.3 Preliminary Checks

Introduction
Before you install the controller, remove the chassis and make any preliminary checks
necessary that are listed in Table 2-2. Figure 2-2 shows the locations for jumper
placements.
Check
Preliminary Check
Number
Input I Jumper Placement
1
Limit Control Relay 1
2
Alarm Relay Action.
3
Note: Solid State and Open Collector must have jumper set to N.O. (Normally Open).
6
Table 2-2 Preliminary Checks
Check the internal jumper for INPUT 1 to make sure it
is set for the correct input type. The jumper is located at
position S101 on the printed wiring board. Figure 2-2
shows the location of the jumper and position
selections.
Check the internal jumper (W101) for CONTROL. The
relay is shipped as N.O. (Normally Open). Figure 2-2
shows the location of the jumper and position
selections.
See Table 2-3 for Limit Control Relay contact
information
The controller has been shipped with ALARM relays
configured for N.C. (Normally Closed). If you want to
change to N.O. refer to Figure 2-2, Jumper positions
W201 and W202:
W201 is the ALARM RELAY 1 jumper.
W202 is the jumper for ALARM RELAY 2.
See Table 2-3 for Limit Control Relay contact
information, and Table 2-4 for Alarm Relay contact
information.
See Alarm Relay Caution Note, Page 8.
UDC2300 Limit Controller Product Manual
Description
1/01