Prompt
Description
Input 1 High Range
IN1 HI
Value
IN1 LO
Input 1 Low Range
Value
Bias on Input 1
BIAS 1
Filter for Input 1
FILTR1
BRNOUT
Burnout Protection
(Sensor Break)
Emissivity
EMISS
Power Line
FREQ
Frequency
1/01
Selection or Range of Setting
Range of Setting:
−999 to 9999. floating in engineering units
Linear Ranges Only
Range of Setting:
−999 to 9999. floating in engineering units
Linear Ranges Only
Range of Setting:
-999 to 9999 (Non-FM)(Engineering Units)
-10 to 10 (FM Models)
A software digital filter is provided for input 1 to
smooth the input signal. You can configure the
first order lag time constant from 1 to 120
seconds
Range of Setting:
0 to 120 seconds
0 = No Filter
UP - UPSCALE BURNOUT is provided for high
limit control.
DOWN - DOWNSCALE BURNOUT is provided
for low limit control.
Emissivity is a correction factor applied to the
Radiamatic input signal that is the ratio of the
actual energy emitted from the target to the
energy which would be emitted if the target were
a perfect radiator.
Range of Setting:
0.01 to 1.00 (RADH and RADI only)
Select whether your controller is operating at 60
Hz or 50 Hz.
60
50
For units powered by +24 Vdc, this configuration
should be set to the AC Line frequency used to
produce the +24 Vdc Supply. Failure to set this
parameter properly can cause normal mode
noise problems in the input readings.
UDC2300 Limit Controller Product Manual
Configuration
Factory
Setting
2400
0
0.0
1.0
UP
1.0
60
27