Honeywell UDC2300 Product Manual page 38

Universal digital controller
Hide thumbs Also See for UDC2300:
Table of Contents

Advertisement

Configuration
Prompt
Description
Word/Byte Order
WS FLT
for floating point
communications
data
UNITS
Communications
Override Units
Local Loopback
LOOPBK
Test
30
Selection or Range of Setting
Byte
0
1
2
3
Choice
FP_B
FPBB
FP_L
FPLB
FP_B
Floating point big endian
FPBB
Floating point big endian with byte-
swapped
FP_L
Floating point little endian
FPLB
Floating point little endian with byte-
swapped
This selection determines how the controller
values are expressed during communications.
PCT
Percent
Eng
Engineering Units
Allows loopback test. The UDC goes into
Loopback mode in which it sends and receives its
own message. The UDC displays PASS or FAIL
status in the upper display and LOOPBACK in
the lower display while the test is running. The
UDC will go into manual mode. The test will run
until the operator disables it here, or until power
is turned off and on.
The UDC does not have to be connected to the
RS-485 link to perform this test. If it is connected,
only one UDC2300 should run the loopback test
at a time. The computer should not be
transmitting on the link while the loopback test is
active.
DIS
Disable
EnAB
Enable
UDC2300 Limit Controller Product Manual
Contents
seeeeeee
emmmmmmm
mmmmmmmm
mmmmmmmm
Byte Order
0123
1032
3210
2301
Factory
Setting
FP_B
PCT
DIS
1/01