Input Calibration

INPUT CALIBRATION MAY REQUIRE ACCESS TO HAZARDOUS LIVE CIRCUITS, AND
SHOULD ONLY BE PERFORMED BY QUALIFIED SERVICE PERSONNEL. MORE THAN
ONE SWITCH MAY BE REQUIRED TO DE-ENERGIZE UNIT BEFORE CALIBRATION.

5.1 Overview

Introduction
This section describes the field calibration procedures for Input 1.
• All input actuations in every UDC2500 controller are fully factory-calibrated and are
ready for configuration by the user.
• Field Calibration can improve the accuracy of the Controller if necessary for a
particular application.
CAUTION
The field calibration will be lost if a change in input type configuration is implemented at a later
time. The original factory calibration data remains available for later use after a field calibration
is done. See subsection 5.6 if you want to restore factory calibration values.
What's in this section?
The following topics are covered in this section.
5.1 Overview
5.2 Minimum and Maximum Range Values
5.3 Preliminary Information
5.4 Input #1 Set Up Wiring
5.5 Input #1 Calibration Procedure
5.6 Restore Factory Calibration
5 Input Calibration
WARNING—SHOCK HAZARD
TOPIC
UDC2500 Universal Digital Limit ControllerProduct Manual
See Page
58
59
61
62
66
67