Permitted ambient temperature
The SINAUT ST7 components can be operated in the same temperature range specified for
the S7-300.
Table 4- 20
Dimensions for installing the SINAUT TIM modules
Table 4- 21
Module
Communications module
TIM 3V-IE and
TIM 3V-IE Advanced
Communications module
TIM 4 and TIM 4R-IE
4.5.6

Connecting the TIM to the power supply

Connecting the TIM module to a live power supply can damage the module. Connect the
module to the power supply only when the power supply is off.
Station control system
System Manual, 07/2009, C79000-G8976-C178-07
Permitted ambient temperatures for the SINAUT TIM modules
Installation position
TIM
Horizontally installed rack
Vertically installed rack
Dimensions for installing the SINAUT TIM modules
WARNING
Permitted ambient temperature (operation)
0 to 60 °C
0 to 40 °C
Module width
Module height
40 mm
125 mm
80 mm
125 mm
Installing and putting a TIM into operation
Max. depth
120 mm or 150 mm with
open front panel
120 mm or 180 mm with
open front panel
4.5 Installing a TIM
165