Installing optional modules
Disconnect the drive from the power line. Lock the main disconnecting device and ensure
by measuring that there is no voltage.
Option slot 2 (I/O extension modules)
1. Put the module carefully into its position on the control unit.
2. Tighten the mounting screw.
3. Tighten the grounding screw (CHASSIS). Note: The screw grounds the module. It is
necessary for fulfilling the EMC requirements and for proper operation of the module.
Option slot 1 (fieldbus adapter modules)
1. Put the module carefully into its position on the control unit.
2. Tighten the mounting screw (CHASSIS). Note: The screw tightens the connections
and grounds the module. It is necessary for fulfilling the EMC requirements and for
proper operation of the module.
Wiring the optional modules
See the appropriate optional module manual for specific installation and wiring
instructions.
Installation instructions 87