Pnp Configuration For Digital Inputs (Digital In); Npn Configuration For Digital Inputs (Digital In); Connection For Obtaining 0 - ABB ACS580-04 Hardware Manual

Drive modules (200 to 500 kw)
Hide thumbs Also See for ACS580-04:
Table of Contents

Advertisement

84 Installation instructions

PNP configuration for digital inputs (DIGITAL IN)

Internal and external +24 V power supply connections for PNP configuration are shown in
the figure below.
Internal +24 V power supply
PNP connection (source)
10
+24V
11
DGND
12
DCOM
13
DI1
14
DI2
15
DI3
16
DI4
17
DI5
18
DI6

NPN configuration for digital inputs (DIGITAL IN)

Internal and external +24 V power supply connections for NPN configuration are shown in
the figure below.
Internal +24 V power supply
NPN connection (sink)
10
+24V
11
DGND
12
DCOM
13
DI1
14
DI2
15
DI3
16
DI4
17
DI5
18
DI6
Connection for obtaining 0...10 V from analog output 2 (ANALOG IN/OUT)
To obtain 0...10 V from analog output AO2, connect a 500 ohm resistor (or two 1 kohm
resistors in parallel) between the analog output 2 AO2 and analog common ground AGND.
Examples are shown in the figure below.
500 ohm
1 kohm
1 kohm
External +24 V power supply
PNP connection (source)
0 V DC
+24 V DC
External +24 V power supply
NPN connection (sink)
+24 V DC
0 V DC
8 AO2
Analog output 2. Default output 0...20 mA.
Analog common ground. Internally connected to chassis
9 AGND
through a 2 Mohm resistor.
8 AO2
Analog output 2. Default output 0...20 mA.
Analog common ground. Internally connected to chassis
9 AGND
through a 2 Mohm resistor.
10
+24V
11
DGND
12
DCOM
13
DI1
14
DI2
15
DI3
16
DI4
17
DI5
18
DI6
10
+24V
11
DGND
12
DCOM
13
DI1
14
DI2
15
DI3
16
DI4
17
DI5
18
DI6