Connecting The Power Cables; Connection Diagram - ABB ACS580-04 Hardware Manual

Drive modules (200 to 500 kw)
Hide thumbs Also See for ACS580-04:
Table of Contents

Advertisement

Connecting the power cables

Connection diagram

ACS580-04
1
For alternatives, see section
example of this chapter, the disconnecting device is not in the same cubicle with the drive module.
2
If a shielded cable is used (not required but recommended) and the conductivity of the shield is
< 50% of the conductivity of the phase conductor, use a separate PE cable (2a) or a cable with a
grounding conductor (2b).
3
We recommend 360-degree grounding at the cabinet entry if a shielded cable is used. Ground the
other end of the input cable shield or PE conductor at the distribution board.
4
We recommend 360-degree grounding at the cabinet entry, see page
(PE)
PE
(PE)
L2
L3
L1
2a
2b
3
L1
L2
L3
PE
L1/
L2/
L3/
U1
V1
W1
INPUT
OUTPUT
T1/
T2/
T3/
U2
V2
W2
4
V1
W1
U1
~
3
M
Selecting the supply disconnecting device
Installation instructions 77
1
8
UDC-
UDC+
PE
6
7
5
on page
40.
9
50.
In the installing