142 Safe torque off function

Operation principle

1. The Safe torque off activates (the activation switch is opened, or safety relay contacts
open).
2. STO inputs on the drive control unit de-energize.
3. The control unit cuts off the control voltage from the drive IGBTs.
4. The control program generates an indication as defined by parameter 31.22 – see
ACS580 firmware manual (3AXD50000016097[English]).
5. Motor coasts to stop (if running). The drive cannot restart while the activation switch or
safety relay contacts are open. After the contacts close, a new start command is
required to start the drive.

Start-up including acceptance test

To ensure the safe operation of a Safe torque off function, validation is required. The final
assembler of the machine must validate the function by performing an acceptance test.
The acceptance test must be performed
at initial start-up of the safety function
after any changes related to the safety function (circuit boards, wiring, components,
settings, etc.)
after any maintenance work related to the safety function.

Competence

The acceptance test of the safety function must be carried out by a competent person with
adequate expertise and knowledge of the safety function as well as functional safety, as
required by IEC 61508-1 clause 6. The test procedures and report must be documented
and signed by this person.

Acceptance test reports

Signed acceptance test reports must be stored in the logbook of the machine. The report
shall include documentation of start-up activities and test results, references to failure
reports and resolution of failures. Any new acceptance tests performed due to changes or
maintenance shall be logged into the logbook.

Acceptance test procedure

After wiring the Safe torque off function, validate its operation as follows.
Action
WARNING! Obey the safety instructions in chapter
injury or death, or damage to the equipment can occur.
Make sure that the drive can be run and stopped freely during start-up.
Stop the drive (if running), switch the input power off and isolate the drive from the power line by a
disconnector.
Check the Safe torque off circuit connections against the circuit diagram.
Close the disconnector and switch the power on.
Safety instructions.
If you ignore them,