64 Guidelines for planning the electrical installation

Example bypass connection

An example bypass connection is shown below.
Q1
Drive main switch
Q4
Bypass circuit breaker
K1
Drive main contactor
K4
Bypass contactor
K5
Drive output contactor
S11
Drive main contactor on/off control
S40
Motor power supply selection (drive or direct-on-line)
S41
Start when motor is connected direct-on-line
S42
Stop when motor is connected direct-on-line

Switching the motor power supply from drive to direct-on-line

1. Stop the drive and the motor with the drive control panel (drive in the local control
mode) or the external stop signal (drive in the remote control mode).
2. Open the main contactor of the drive with S11.
3. Switch the motor power supply from the drive to direct-on-line with S40.
4. Wait for 10 seconds to allow the motor magnetization to die away.
5. Start the motor with S41.