152 Optional I/O extension modules
Relay output connection example
24 V DC
Digital input connection example
230 V AC source
Start-up
Setting the parameters
1. Power up the drive.
2. If no warning is shown,
•
make sure that the value of both parameter 15.02 Detected extension module and
parameter 15.01 Extension module type is CHDI-01.
If warning A7AB Extension I/O configuration failure is shown,
•
make sure that the value of parameter 15.02 Detected extension module is CHDI-
01.
•
set parameter 15.01 Extension module type to CHDI-01.
You can now see the parameters of the extension module in parameter group 15 I/O
extension module.
3. Set the parameters of the extension module to applicable values.
Parameter setting example for relay output
This example shows how make relay output RO4 of the extension module indicate the
reverse direction of rotation of the motor with a one-second delay.
Parameter
15.07 RO4 source
15.08 RO4 ON delay
15.09 RO4 OFF delay
Diagnostics
Faults and warning messages
Warning A7AB Extension I/O configuration failure.
RO4C
50
RO4A
51
RO4B
52
CHDI-01
65
HDI7
66
HDI8
67
NEUTRAL
CHDI-01
Setting
Reverse
1 s
1 s