120 Technical data

Ambient conditions

Installation site altitude
Air temperature
Relative humidity
Contamination levels
(IEC 60721-3-3,
IEC 60721-3-2,
IEC 60721-3-1)
Atmospheric pressure
Vibration (IEC 60068-2-6.
Test Fc)
Shock (IEC 60068-2-27)
Free fall
Environmental limits for the drive are given below. The drive is to be used in a
heated, indoor, controlled environment.
Operation
installed for stationary
use
For TN and TT neutral-
grounded network
systems and IT non-
corner grounded
network systems:
0 to 4000 m (13123 ft)
above sea level
For TN, TT and IT
corner-grounded
network systems:
0 to 2000 m (6561 ft)
above sea level
Above 1000 m [3281 ft]),
see page 114.
-15 to +55 °C
(5 to 131 °F). No frost
allowed. See page 114.
5 to 95%
No condensation allowed. Maximum allowed relative humidity is 60% in the
presence of corrosive gases.
No conductive dust allowed.
Chemical gases:
Class 3C2
Solid particles:
Class 3S2
70 to 106 kPa
0.7 to 1.05 atmospheres
Max. 0.1 mm (0.004 in.)
(10 to 57 Hz),
2
2
max. 10 m/s
(33 ft/s
)
(57 to 150 Hz) sinusoidal
Not allowed
Not allowed
Storage
in the protective
package
-
-40 to +70 °C
(-40 to +158 °F)
Max. 95%
Chemical gases:
Class 1C2
Solid particles:
Class 1S3
70 to 106 kPa
0.7 to 1.05 atmospheres
Max. 1 mm (0.04 in.)
(5 to 13.2 Hz),
2
2
max. 7 m/s
(23 ft/s
)
(13.2 to 100 Hz)
sinusoidal
2
Max. 100 m/s
2
(330 ft./s
), 11 ms
100 mm (4 in.) for weight
over 100 kg (220 lb)
Transportation
in the protective
package
-
-40 to +70 °C
(-40 to +158 °F)
Max. 95%
Chemical gases:
Class 2C2
Solid particles:
Class 2S2
60 to 106 kPa
0.6 to 1.05 atmospheres
Max. 3.5 mm (0.14 in.)
(2 to 9 Hz),
2
2
max. 15 m/s
(49 ft/s
)
(9 to 200 Hz) sinusoidal
2
Max. 100 m/s
2
(330 ft./s
), 11 ms
100 mm (4 in.) for weight
over 100 kg (220 lb)