Connect the test line according to the figure.
Set parameters: F0.03 = 8 (PV settings))
F0.11 = 4 (keyboard + Terminal + communication);
F1.00 = 1 (forward run);
F1.01 = 8 (freewheel);
F1.10 = 2 (three-wire mode 1)
E3.02 = 3 (three-wire operation control);
E3.05 = 00100;
E0.00 = 2 (MPPT mode);
After setting the parameters, press the RUN key, frequency inverter runs. If water
reaches the high lever detection point, the frequency inverter will free stop. When the
water level falls below the low level detection point, the frequency inverter
automatically starts running.
(3)Water level detection mode 2- Analog detection.
When using analog detection,AI terminals will lead to the detection line and connect
to the cable according to the wiring diagram. Water-filled test point voltage is 7V. When
AI1 detects 7V voltage, the freq frequency inverter will free stop. When AI1 detects
voltage is lower than 3V , the frequency inverter automatically starts running.
High level
detection point
DI2
frequency
COM
inverter
DI1
Low level
detection point
High level
+10V
detection points
frequency
AI1
inverter
Low level
GND
detection points
Chapter8.Installation and Spare Circuit
Water
Tower
(7V)
+10V
Water
Tower
GND
(3V)
77