Chapter5.Function parameter
Motor
39
overtemperature pre-
warning
Current running time
40
arrival
High-speed pulse output
F2.06
function selection
DA1 output function
F2.07
selection
DA2 output function
F2.08
selection
High-speed pulse output frequency range is 0.01kHz to F2.09 (maximum frequency
of high-speed pulse output), F2.09 can be set between 0.01kHz to 100.00kHz.
Analog output DA1 and DA2 output range is 0V to 10V, or 0mA to 20mA. The range
of pulse output or analog output and the corresponding calibration relation are shown in
the following table:
Set
Function
value
0
Running frequency
1
Set frequency
2
Output current
3
Output torque
4
Output power
5
Output voltage
High-speed pulse
6
input
7
AI1
8
AI2
9
Reserved
10
Reserved
11
Reserved
Communication
12
setting
13
Motor speed
14
Output current
15
DC bus voltage
16
Reserved
Frequency source
17
main set
Maximum output
F2.09
frequency of high-speed
When the motor temperature reaches
F8.35 (motor overheat pre-alarm threshold),
the output ON signal. (Motor temperature by
d0.41 view)
Outputs ON signal when the inverter's
current running time exceeds the set time by
F7.45.
0 to 17
0 to 17
0 to 17
Description
0 to maximum output frequency
0 to maximum output frequency
0 to 2 times rated motor current
0 to 2 times rated motor torque
0 to 2 times rated power
0 to 1.2 times rated inverter voltage
0.01kHz to 100.00kHz
0V to 10V
0V to 10V (or 0 to 20mA)
0.0% to 100.0%
0
to speed with maximum output
frequency
0.0A to 100.0A (inverter power ≦
55kW); 0.0A to 1000.0A (inverter power>
55kW)
0.0V to 1000.0V
0~max output frequency
0.01kHz to 100.00kHz
36
0
0
1
50.00kHz ☆