Powtran PI9000-S Series User Manual page 101

Frequency inverter
Table of Contents

Advertisement

Whenthe function code is set to valid, if the interval time between one communication and the next
communication exceeds the communication time-out time, the system will report communication
failure error (Fault ID Err.16). Generally, it is set to invalid. If the parameter can be set to monitor
the communication status in continuous communication system.
Communication
protocol selection
F9.05
Setting range
F9
.05=1: select standard Modbus protocol.
F9
.05=0: when reading command, the number of bytes returned by slave is more 1 byte than
standard Modbus protocol.
Communication read
current resolution
F9.06
Setting range
Used to determine the current output units when communication reads output current.
Default
0: non-standard Modbus protocol
protocol
1: standard Modbus
Default
0: 0.01A
1: 0.1A
97
Appendix II
0
0