Powtran PI9000-S Series User Manual page 76

Frequency inverter
Table of Contents

Advertisement

Chapter8.Installation and Spare Circuit
Function description of main circuit terminal
Terminals
R/L1
S/L2
T/L3
/E
P+, RB
U/T1
V/T2
W/T3
P+, P-
P, P+
Description of control circuit terminals
Categ
Symbol
ory
+10V-
GND
Power
+24V-
supply
COM
PLC
AI1-GND
Analog
input
AI2-GND
Digital
DI1
Name
Inverter input
terminals
Ground terminals
Braking resistor
terminals
Output terminals
DC bus output
terminals
DC reactor
terminals
Name
External+
10V power
supply
External+24V
power supply
External
power input
terminal
Analog input
terminal 1
Analog input
terminal 2
Digital input 1
Description
Connect to three-phase power
supply, single-phase connects to R,
T;PV voltage connects to R, T
Connect to ground
Connect to braking resistor
Connect to three-phase motor
Connect to braking unit
Connect to DC reactor(remove the
shorting block)
Output +10V power supply, maximum
output current: 10mA
Generally it is used as power supply of
external potentiometer, potentiometer
resistance range: 1kΩ to 5kΩ
Output +24V power supply, generally it is
used as power supply of digital input and
output terminals and external sensor.
Maximum output current: 200mA
When external signal is used to drive,
please unplug J5 jumpers , PLC must be
connected to external power supply, and to
+24V (default).
1.Input range:(DC 0V to 10V/0 to 20mA),
depends on the selected J3 jumper on
control panel.
2.Input impedance: 22kΩ with voltage
input, 500Ω with current input.
1.Input range:(DC 0V to 10V/0 to 20mA),
depends on the selected J4 jumper on
control panel.
2.Input impedance: 22kΩ with voltage
input, 500Ω with current input.
1.Opto-coupler isolation, compatible with
72
Function

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents