11
Err.11
Motor Overload
12
Err.12
Input phase loss
Output phase
13
Err.13
14
Err.14
overheating
15
Err.15
equipment fault
occurs
1. power grid voltage is
too low
2.whether the setting
motor protection
parameters (F8.03) is
appropriate or not
3.whether the load is too
large or the motor stall
occurs
1.the drive panel is
abnormal.
2.the lightning protection
plate is abnormal
3.the main control panel
is abnormal
4.the three-phase input
power is not normal
1.the lead wires from the
inverter to the motor is
not normal
2.the inverter's three
phase output is
unbalanced when the
loss
motor is running
3.the drive panel is
abnormal.
4.the module is
abnormal
1.the air duct is blocked
2.the fan is damaged
3.the ambient
Module
temperature is too high
4.the module thermistor
is damaged
5.the inverter module is
damaged
Input external fault signal
External
through the multi-function
terminal DI
67
Chapter7.Troubleshooting
mechanical conditions
1.check the power grid
voltage
2.correctly set this
parameter.
3.reduce the load and
check the motor and its
mechanical conditions
1.replace the drive, the
power board or contactor
2.seek for technical
support
3.check and eliminate
the existing problems in
the peripheral line
1.eliminate peripheral
faults
2.check the motor's
three-phase winding is
normal or not and
eliminate faults
3.seek for technical
support
1.clean up the air duct
2.replace the fan
3.decrease the ambient
temperature
4.replace the thermistor
5.replace the inverter
module
Reset run