Appendix B - Ccn Tables - Carrier AQUASNAP 30RAP010-150 Controls, Start-Up, Operation, Service, And Troubleshooting

Air-cooled chillers with puron refrigerant (r-410a)
Table of Contents

Advertisement

CCN DISPLAY TABLES — A_UNIT (General Unit Parameters)
DESCRIPTION
Control Mode
Occupied
CCN Chiller
Low Sound Active
Alarm State
Active Demand Limit
Override Modes in Effect
Percent Total Capacity
Requested Stage
Active Set Point
Control Point
Entering Fluid Temp
Leaving Fluid Temp
Emergency Stop
Minutes Left for Start
PUMPS
Cooler Pump Relay 1
Cooler Pump Relay 2
Cooler Pump 1 Interlock
Cooler Pump 2 Interlock
Cooler Flow Switch
Lead Pump
Rotate Cooler Pumps Now
Heat/Cool Select
CCN DISPLAY TABLES — CIRCA_AN (Circuit A Analog Parameters)
DESCRIPTION
CIRCUIT A ANALOG VALUES
Percent Total Capacity
Percent Available Cap.
Discharge Pressure
Suction Pressure
Head Setpoint
Saturated Condensing Tmp
Saturated Suction Temp
EXV% Open
Var Head Press Output
Compr Return Gas Temp
Discharge Gas Temp
Suction Superheat Temp
Spare 1 Temperature
APPENDIX B — CCN TABLES
VALUE
0 = Test
1 = Local Off
2 = CCN Off
3 = Clock Off
4 = Emergency Stop
5 = Local On
6 = CCN On
7 = Clock On
8 = Heat Enabled
9 = Pump Delay
No/Yes
Start/Stop
No/Yes
Normal/Alert/Alarm
0 to 100
No/Yes
0 to 100
0 to 99
–20 to 70
–20 to 70
snnn.n
snnn.n
Enable/Emstop
00:00 to 15:00
Off/On
Off/On
Open/Close
Open/Close
Open/Close
No/Yes
Heat/Cool
VALUE
0-100
0-100
nnn.n
nnn.n
nnn.n
snnn.n
snnn.n
nnn
nnn.n
nnn.n
nnn.n
nnn.n
nnn.n
100
UNITS
POINT NAME
STAT
OCC
CHIL_S_S
LSACTIVE
ALM
%
DEM_LIM
MODE
%
CAP_T
STAGE
F
SP
F
CTRL_PNT
F
EWT
F
LWT
Enable
EMSTOP
minutes
MIN_LEFT
COOLPMP1
COOLPMP2
PMP1_FBK
PMP2_FBK
COOLFLOW
LEADPUMP
ROT_PUMP
HC_SEL
UNITS
POINT NAME
%
CAPA_T
%
CAPA_A
PSIG
DP_A
PSIG
SP_A
°F
HSP
F
TMP_SCTA
F
TMP_SSTA
%
EXV_A
milliamps
VHP_ACT
F
TMP_RGTA
°F
DISGAS
F
SH_A
°F
SPR1_TMP
FORCIBLE
N
N
Y
N
N
Y
N
N
N
N
Y
N
N
Y
N
N
N
N
N
N
N
Y
N
FORCIBLE
N
N
N
N
N
N
N
N
N
N
N
N
N