Carrier AQUASNAP 30RAP010-150 Controls, Start-Up, Operation, Service, And Troubleshooting page 78

Air-cooled chillers with puron refrigerant (r-410a)
Table of Contents

Advertisement

ALARM/
ALARM
ALERT
OR
DESCRIPTION
CODE
ALERT
Current Sensor Board
T501
Alert
A1 Failure
Current Sensor Board
T502
Alert
A2 Failure
Current Sensor Board
T503
Alert
A3 Failure
Current Sensor Board
T505
Alert
B1 Failure
Current Sensor Board
T506
Alert
B2 Failure
Current Sensor Board
T507
Alert
B3 Failure
T950
Alert
Loss of Communication
with Water System
Manager
A951
Alert
Loss of Communication
with Chillervisor System
Manager
T952
Alert
Loss of Communication
with Hydronic System
Manager
LEGEND
CCN
— Carrier Comfort Network
CSB
— Current Sensor Board
CSM
— Chillervisor System Manager
CXB
— Current Sensor Board
EEPROM — Electronic Erasable Programmable Read Only Memory
EMM
— Energy Management Module
EWT
— Entering Fluid Temperature
EXV
— Electronic Expansion Valve
HSM
— Hydronic System Manager
LCW
— Leaving Chilled Water
LWT
— Leaving Fluid Temperature
MBB
— Main Base Board
OAT
— Outdoor-Air Temperature
SCT
— Saturated Condensing Temperature
WSM
— Water System Manager
Table 36 — Alarm and Alert Codes (cont)
WHY WAS THIS
ALARM
GENERATED?
Alert occurs when CSB out-
Compressor A1 shut
put is a constant high value
down
Alert occurs when CSB out-
Compressor A2 shut
put is a constant high value
down
Alert occurs when CSB out-
Compressor A3 shut
put is a constant high value
down
Alert occurs when CSB out-
Compressor B1 shut
put is a constant high value
down
Alert occurs when CSB out-
Compressor B2 shut
put is a constant high value
down
Alert occurs when CSB out-
Compressor B3 shut
put is a constant high value
down
No communications have
WSM forces removed.
been received by the MBB
Chiller runs under own
within 5 minutes of last
control
transmission
No communications have
CSM forces removed.
been received by the MBB
Chiller runs under own
within 5 minutes of last
control
transmission
No communications have
HSM forces removed.
been received by the MBB
Chiller runs under own
within 5 minutes of last
control
transmission
78
ACTION TAKEN
RESET
BY CONTROL
METHOD
Automatic
Automatic
Automatic
Automatic
Automatic
Automatic
Automatic
Automatic
Automatic
PROBABLE
CAUSE
CSB failure.
Wiring error.
CSB failure.
Wiring error.
CSB failure.
Wiring error.
CSB failure.
Wiring error.
CSB failure.
Wiring error.
CSB failure.
Wiring error.
Failed module, wiring
error, failed
transformer, loose
connection plug,
wrong address
Failed module, wiring
error, failed
transformer, loose
connection plug,
wrong address
Failed module, wiring
error, failed
transformer, loose
connection plug,
wrong address