Component Test - Carrier AQUASNAP 30RAP010-150 Controls, Start-Up, Operation, Service, And Troubleshooting

Air-cooled chillers with puron refrigerant (r-410a)
Table of Contents

Advertisement

III. Unit Start-Up (cont)

COMPONENT TEST

USE ESCAPE/ARROW KEYS TO ILLUMINATE CONFIGURATION LED. PRESS ENTER TO DISPLAY 'DISP'.
PRESS ENTER AGAIN TO DISPLAY 'TEST' FOLLOWED BY 'OFF'. PRESS ENTER TO STOP DISPLAY AT
'OFF' AND ENTER AGAIN SO 'OFF' DISPLAY FLASHES. 'PASS' AND 'WORD' WILL FLASH IF PASSWORD
NEEDS TO BE ENTERED. PRESS ENTER TO DISPLAY PASSWORD FIELD AND USE THE ENTER KEY FOR
EACH OF THE FOUR PASSWORD DIGITS. USE ARROW KEYS IF PASSWORD IS OTHER THAN STANDARD.
AT FLASHING 'OFF' DISPLAY, PRESS THE UP ARROW KEY TO DISPLAY 'ON' AND PRESS ENTER. ALL LED
SEGMENTS AND MODE LEDS WILL LIGHT UP. PRESS ESCAPE TO STOP THE TEST. PRESS ESCAPE TO
RETURN TO THE 'DISP' DISPLAY. PRESS THE ESCAPE KEY AGAIN AND USE THE ARROW KEYS TO ILLU-
MINATE THE SERVICE TEST LED. PRESS ENTER TO DISPLAY 'TEST'. PRESS ENTER TO STOP DISPLAY
AT 'OFF' AND ENTER AGAIN SO 'OFF' FLASHES. PRESS THE UP ARROW KEY AND ENTER TO ENABLE
THE MANUAL MODE. PRESS ESCAPE AND DISPLAY NOW SAYS 'TEST' 'ON'. REFER TO THE TABLE
BELOW.
KEYPAD
SUB-MODE
ENTRY
ENTER
TEST
OUTS
ENTER
NOTE: If the unit has a single circuit, the Circuit B items will not appear in the display.
Service Test Mode and Sub-Mode Directory
ITEM
DISPLAY
ON/OFF
SERVICE TEST MODE
OUTPUTS AND PUMPS
EXV.A
xxx%
EXV.B
xxx%
FAN1
ON/OFF
FAN 1 RELAY
FAN2
ON/OFF
FAN 2 RELAY
FAN3
ON/OFF
FAN 3 RELAY
FAN4
ON/OFF
FAN 4 RELAY
FAN5
ON/OFF
FAN 5 RELAY
FAN6
ON/OFF
FAN 6 RELAY
FAN7
ON/OFF
FAN 7 RELAY
FAN8
ON/OFF
FAN 8 RELAY
V.HPA
xx
VAR HEAD PRESS% CIRCUIT A
V.HPB
xx
VAR HEAD PRESS% CIRCUIT B
CLP.1
ON/OFF
COOLER PUMP RELAY 1
CLP.2
ON/OFF
COOLER PUMP RELAY 2
COMPRESSOR A1 LOAD
DIG.P
xxx
CL.HT
ON/OFF
COOLER/PUMP HEATER
CCH.A
ON/OFF
CRANKCASE HEATER CIRCUIT A
CCH.B
ON/OFF
CRANKCASE HEATER CIRCUIT B
RMT.A
ON/OFF
REMOTE ALARM RELAY
ITEM
EXPANSION
To Enable Service Test Mode, move
Enable/Off/Remote Contact switch to
OFF. Change TEST to ON. Move
switch to ENABLE.
EXV% OPEN
EXV% OPEN
Condenser fan contactor 1
Condenser fan contactor 2
Condenser fan contactor 3
Condenser fan contactor 4
Condenser fan contactor 5
Condenser fan contactor 6
Condenser fan contactor 7
Condenser fan contactor 8
Digital Scroll option only
PERCENT
CL-10
Completed
COMMENT
(Yes/No)

Hide quick links: