Appendix A — Ccn Tables - Carrier Air Conditioner Operation And Service Manual

Air-cooled reciprocating liquid chillers with comfortlink controls 50/60 hz
Hide thumbs Also See for Air Conditioner:
Table of Contents

Advertisement

CSM/FSM EQUIPMENT TABLE (Type 621H, Block 2)
LINE
1
2
3
4
5
6
7
8
9
WSM EQUIPMENT PART COOL SOURCE MAINTENANCE TABLE
DESCRIPTION
WSM Active?
Chilled water temp
Equipment status
Commanded state
CHW setpoint reset value
Current CHW setpoint
DESCRIPTION
Current Mode (1=Occup.)
Current Occup. Period #
Timed-Override in Effect
Time-Override Duration
Current Occupied Time
Current Unoccupied Time
Next Occupied Day
Next Occupied Time
Next Unoccupied Day
Next Unoccupied Time
Previous Unoccupied Day
Previous Unoccupied Time
APPENDIX A — CCN TABLES (cont)
DESCRIPTION
Chiller Status
0 = Chiller is off
1 = Valid run state in CCN mode
2 = Recycle active
3 = Chiller is in Local Mode
4 = Power Fail Restart in Progress
5 = Shutdown due to fault
6 = Communication Failure
Lag Status
Percent Total Capacity Running
Service Runtime
unused
unused
unused
Power Fail Auto Restart
Percent Available Capacity On
SUPERVISOR MAINTENANCE TABLE
OCCUPANCY MAINTENANCE TABLE
OCCUPANCY SUPERVISORY
79
STATUS
Yes
snn.n °F
On
Enable/Disable/None
nn.n^F
snn.n °F
STATUS
0,1
0-8
Yes/No
0-4 hours
hh:mm
hh:mm
hh:mm
hh:mm
hh:mm
POINT
CHILSTAT
LAGSTAT
CAP_T
HR_MACH
ASTART
CAP_A
POINT
WSMSTAT
CHWTEMP
CHLRST
CHLRENA
CHWRVAL
CHWSTPT
POINT
MODE
PER-NO
OVERLAST
OVR_HRS
STRTTIME
ENDTIME
NXTOCDAY
NXTOCTIM
NXTUNDAY
NXTUNTIM
NXTUNDAY
PRVUNTIM

Hide quick links: