Carrier AQUASNAP 30RAP010-150 Controls, Start-Up, Operation, Service, And Troubleshooting page 90

Air-cooled chillers with puron refrigerant (r-410a)
Table of Contents

Advertisement

Configuration Mode and Sub-Mode Directory (cont)
SUB-MODE
OPT2
LS.MD
CCN
APPENDIX A — DISPLAY TABLES (cont)
ITEM
DISPLAY
CTRL
X
LOAD
X
LLCS
X
LCWT
XX
DELY
XX
ICE.M
ENBL/DSBL
X
LS.ST
00:00
LS.ND
00:00
LS.LT
XXX%
CCNA
XXX
CCNB
XXX
BAUD
X
ITEM DESCRIPTION
UNIT OPTIONS 2 CONTROLS
Control Method
Loading Sequence Select
Lead/Lag Circuit Select
High LCW Alert Limit
Minutes Off Time
Ice Mode Enable
Low Sound Mode Select
Low Sound Start Time
Low Sound End Time
Low Sound Capacity Limit
CCN NETWORK CONFIGS
CCN Address
CCN Bus Number
CCN Baud Rate
90
COMMENT
Default: 0
0 = Enable/Off/Remote Switch
2 = Occupancy
3 = CCN Control
Default: 1
1 = Equal
2 = Staged
Default: 1
1 = Automatic
2 = Circuit A Leads
3 = Circuit B Leads
Default: 60 F
Range: 2 to 60 F
Default: 0 Minutes
Range: 0 to 15 Minutes
Default: Disable
Default: 0
0 = Mode Disable
1 = Fan Noise Only
2 = Fan/Compressor Noise
Default: 00:00
Default: 00:00
Default: 100%
Range: 0 to 100%
Default: 1
Range: 0 to 239
Default: 1
Range: 0 to 239
Default: 3
1 = 2400
2 = 4800
3 = 9600
4 =19,200
5 =38,400