Carrier AQUASNAP 30RAP010-150 Controls, Start-Up, Operation, Service, And Troubleshooting page 137

Air-cooled chillers with puron refrigerant (r-410a)
Table of Contents

Advertisement

III. Unit Start-Up (cont)
PRESS ESCAPE KEY TO DISPLAY 'RSET'. PRESS DOWN ARROW KEY TO DISPLAY 'SLCT'.
PRESS ENTER KEY.
RECORD CONFIGURATION INFORMATION BELOW:
SUBMODE
SLCT
PRESS ESCAPE KEY SEVERAL TIMES TO GET TO THE MODE LEVEL (BLANK DISPLAY). USE THE
ARROW KEYS TO SCROLL TO THE SET POINT LED. PRESS ENTER TO DISPLAY SETPOINTS.
RECORD CONFIGURATION INFORMATION BELOW:
SUBMODE
COOL
HEAD
FRZ
SLCT (Setpoint and Ramp Load Configuration)
ITEM
ITEM EXPANSION
SETPOINT AND RAMP LOAD
CLSP
COOLING SETPOINT SELECT
RL.S
RAMP LOAD SELECT
CRMP
COOLING RAMP LOADING
SCHD
SCHEDULE NUMBER
Z.GN
DEADBAND MULTIPLIER
ITEM
COOLING SETPOINTS
CSP.1
COOLING SETPOINT 1
CSP.2
COOLING SETPOINT 2
CSP.3
HEAD PRESSURE SETPOINTS
H.DP
F.ON
FAN ON SET POINT
F.OFF
FAN OFF SET POINT
B.OFF
BASE FAN OFF DELTA TEMP
F.DLT
FAN STAGE DELTA
BRINE FREEZE SETPOINT
BR.FZ
BRINE FREEZE POINT
SETPOINT
ITEM EXPANSION
ICE SETPOINT
HEAD SET POINT
CL-9
DISPLAY
ENTRY
X
ENBL/DSBL
X.X
XX
X.X
DISPLAY
ENTRY
XXX.X °F
XXX.X °F
XXX.X °F
XXX.X °F
XXX.X °F
XXX.X °F
XX.X
XX.X
XXX.X °F