Carrier AQUASNAP 30RAP010-150 Controls, Start-Up, Operation, Service, And Troubleshooting page 39

Air-cooled chillers with puron refrigerant (r-410a)
Table of Contents

Advertisement

Table 13 — Dual Chiller Configuration (Master Chiller Example) (cont)
SUB-MODE
ITEM
LLEN
LLEN
MSSL
SLVA
SLVA
RSET
LLBL
LLBL
LLBD
LLDY
LLDY
PARA
NOTES:
1. Master Control Method (CTRL) can be configured as 0-Switch, 2-Occu-
pancy or 3-CCN.
2. Parallel Configuration (PARA) cannot be changed.
KEYPAD ENTRY
DISPLAY
ENTER
CRST
LLEN
ENTER
DSBL
ENTER
DSBL
ENBL
ENTER
ENBL
ESCAPE
LLEN
MSSL
ENTER
MAST
ESCAPE
MSSL
SLVA
ENTER
0
ENTER
0
2
ENTER
2
ESCAPE
SLVA
LLBL
ENTER
0
ENTER
0
2
ENTER
2
ESCAPE
LLBL
LLBD
ENTER
168
ESCAPE
LLBD
LLDY
ENTER
5
ENTER
5
10
ENTER
10
ESCAPE
LLDY
ESCAPE
RSET
ENTER
YES
ITEM EXPANSION
COOLING RESET TYPE
LEAD/LAG CHILLER ENABLE
LEAD/LAG CHILLER ENABLE
MASTER /SLAVE SELECT
MASTER /SLAVE SELECT
SLAVE ADDRESS
SLAVE ADDRESS
LEAD/LAG BALANCE SELECT
LEAD/LAG BALANCE SELECT
LEAD/LAG BALANCE DELTA
LEAD/LAG BALANCE DELTA
LAG START DELAY
LAG START DELAY
39
COMMENTS
15 ITEMS
SCROLLING STOPS
VALUE FLASHES
SELECT ENBL
CHANGE ACCEPTED
DEFAULT MAST
SCROLLING STOPS
VALUE FLASHES
SELECT 2
CHANGE ACCEPTED
SCROLLING STOPS
VALUE FLASHES
SELECT 2 - Automatic
CHANGE ACCEPTED
DEFAULT 168
SCROLLING STOPS
VALUE FLASHES
SELECT 10
CHANGE ACCEPTED
MASTER COMPLETE