Carrier AQUASNAP 30RAP010-150 Controls, Start-Up, Operation, Service, And Troubleshooting page 135

Air-cooled chillers with puron refrigerant (r-410a)
Table of Contents

Advertisement

III. Unit Start-Up (cont)
PRESS ESCAPE KEY TO DISPLAY 'HP.B'. PRESS DOWN ARROW KEY TO DISPLAY 'EXV.A'.
PRESS ENTER KEY.
RECORD CONFIGURATION INFORMATION BELOW.
SUB-MODE
EXV.A
PRESS ESCAPE KEY TO DISPLAY 'EXV.A'. PRESS DOWN ARROW KEY TO DISPLAY 'EXV.B'.
PRESS ENTER KEY.
RECORD CONFIGURATION INFORMATION BELOW.
SUB-MODE
EXV.B
EXV.A (Circuit A EXV Configuration)
ITEM
ITEM EXPANSION
EXV OPENING AT LOW LWT
EXV.L
LWT FOR EXV MIN OPENING
LWT.L
EXV OPENING AT HIGH LWT
EXV.H
LWT FOR EXV MAX OPENING
LWT.H
EXV CIRC.A MIN POSITION
MIN.A
EXVA STEPS IN RANGE
RNG.A
EXVA STEPS PER SECOND
SPD.A
EXVA FAIL POSITION IN%
POF.A
EXVA MINIMUM STEPS
MIN.A
EXVA MAXIMUM STEPS
MAX.A
EXVA OVERRUN STEPS
OVR.A
EXVA STEPPER TYPE
TYP.A
HIGH SCT THRESHOLD
H.SCT
OPEN EXV X% ON 2ND COMP
X.PCT
MOVE EXV X% ON DISCRSOL
X.PER
PRE-OPEN EXV - FAN ADDING
A.PCT
PRE-CLOSE EXV - FAN SUB
M.PCT
PRE-CLOSE EXV - LAG SHUT
S.PCT
LAG START DELAY
DELY
LOW SH DELTA T - EXV MOVE
L.DL.T
EXV RATE THRESHOLD
SHR.T
LOW SH OVERRIDE EXV MOVE
L.EX.M
EXV.B (Circuit B EXV Configuration)
ITEM
ITEM EXPANSION
MIN.B
EXV CIRC.B MIN POSITION
RNG.B
EXVB STEPS IN RANGE
SPD.B
EXVB STEPS PER SECOND
POF.B
EXVB FAIL POSITION IN %
MIN.B
EXVB MINIMUM STEPS
MAX.B
EXVB MAXIMUM STEPS
OVR.B
EXVB OVERRUN STEPS
TYP.B
EXVB STEPPER TYPE
DISPLAY
XX%
XX° F
XX%
XX° F
XXXXX
XXXXX
XXXXX
XXXXX
XX.X F
X.X%
DISPLAY
XXXXX
XXXXX
XXXXX
XXXXX
CL-7
ENTRY
XXX
XXX
XXX
0,1
XXX
XX
XX
XXX
XXX
XXX
XXX
XXX
ENTRY
XXX
XXX
XXX
0,1