Zone Addresses; Zone Numbering System - Honeywell Galaxy 2 Series Installation Manual

Hide thumbs Also See for Galaxy 2 Series:
Table of Contents

Advertisement

Galaxy 2 Series Installation Manual

Zone Addresses

Each zone on the Galaxy 2 Series has a 4-digit address. For example: 1004, 1058. The address is made up of
three reference numbers as shown in the following figure:
Represents Panel
Line No.
The example above, 1004, is the detector connected to line 1, RIO 00, zone 4.

Zone Numbering System

The numbering system is as follows:
1.
The first number is the Galaxy 2 Series Panel line that the RIO/Expander is connected to. This will
always be 1.
2.
The next two numbers refer to the address of the RIO/Expander that the zone is on.
00 = On board RIO
01 = On board RIO
02 = RIO/Expander 1
03 = RIO/Expander 2
04 = RIO/Expander 3
05 = RIO 4
3.
The last number is the actual zone on the RIO/Expander 1-8. Therefore the valid zone numbers are:
1001 - 1004
1011 - 1018
1021 - 1028
1031 - 1038
1041 - 1048
1051 - 1058
This gives a total of 44 zones.
Example: 1004
1 00
Represents
RIO Address
GALAXY
2 Series
PANEL
1
RIO
ADDRESS 00
Figure 10. Zone Addresses
Zone Addresses
4
Represents
Zone No. 1-8 on
RIO/Expander
ZONE 4
15

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents