51 - Parameters (cont'd)
2. End of Line
This option defaults to (1) Double Balanced.
2. EOL Resistor
This selects the resistor value for the end of line (EOL) resistor used in EOL double balance zone configura-
tions. Normally this should be 1000 ohms. The value entered is in hundreds of ohms, 01 = 100 ohms, 99 =
9900 ohms.
3. Contact Res
As for EOL Resistor but for Contact resistor.
47 = Set confirm
This parameter gives an external indication when the system has set. There are three options:
0. Off
1. Strobe (flashes for two seconds)
2. Strobe & Bell (indication for two seconds when set terminates)
50 = RF Options
This parameter has six options:
1. RF Fob Unset
This option assigns the operation of the keyfobs.
0 = Disable fobs
1 = Unset anytime (default)
2 = After Entry
2. Supervision
If no signal is received from each RF detector within this time window, a supervision alarm is generated.
0 = 2.0 hours (default)
1 = 3.6 hours
2 = 8.4 hours
3. Audible Jam
This parameter suppresses alert indications for audible jam faults and has two settings:
0 = No (always silent). This is the default.
1 = Yes (follows alert programming in parameter 23)
4. Audible Supervision
This parameter assigns the indication for supervision loss and has two options:
0 = No (always silent).This is the default
1 = Yes (follows alert programming in parameter 23)
5. Audible RF Low Bat
This parameter assigns the indication for RF low bat faults and has two options:
0 = No (always silent). This is the default.
1 = Yes (follows alert programming in parameter 23)
Galaxy 2 Series Installation Manual