HP P2000 G3 MSA Reference Manual page 56

Hide thumbs Also See for P2000 G3 MSA:
Table of Contents

Advertisement

468
Info.
FPGA temperature has returned to the normal operating range and the speed of buses connecting the
FPGA to downstream adapters has been restored. The speed was reduced to compensate for an FPGA
over-temperature condition.
This event indicates that a problem reported by event 469 is resolved.
Recommended actions
No action is required.
469
Warning
The speed of buses connecting the FPGA to downstream adapters has been reduced to compensate for an
FPGA over-temperature condition.
The storage system is operational but I/O performance is reduced.
Recommended actions
Check that the storage system's fans are running.
Check that the ambient temperature is not too warm. The enclosure operating range is 5
(41
–104
F
F
Check for any obstructions to the airflow.
Check that there is a module or blank plate in every module slot in the enclosure.
If none of the above explanations apply, replace the controller module that logged the error.
When the problem is resolved, event 468 is logged.
471
Info.
A replication was queued because the indicated secondary volume is detached from the replication set.
Recommended actions
No action is required.
To enable the replication to proceed, reattach the secondary volume and then resume the replication.
472
Error
A replication failed to start on the indicated secondary volume.
This can occur when the secondary system is not licensed for replication (for example, a temporary license
expired).
Recommended actions
To perform replication, ensure that the secondary system has a valid replication license.
475
Info.
A replication was queued because the indicated secondary volume is offline.
Recommended actions
No action is required.
To enable the replication to proceed, reattach the secondary volume and then resume the replication.
56
Event descriptions
).
–40
C
C

Advertisement

Table of Contents
loading

Table of Contents