HP P2000 G3 MSA Reference Manual page 13

Hide thumbs Also See for P2000 G3 MSA:
Table of Contents

Advertisement

28
Info.
Controller parameters have been changed.
This event is logged when general configuration changes are made; for example, utility priority, remote
notification settings, user interface passwords, and management port IP values. This event is not logged
when changes are made to vdisk or volume configuration.
Recommended actions
No action is required.
31
Info.
The indicated disk is no longer a global or dedicated spare.
Recommended actions
No action is required.
32
Info.
Vdisk verification has started.
Recommended actions
No action is required.
33
Info.
Controller time/date has been changed.
This event is logged before the change happens, so the timestamp of the event shows the old time. This
event may occur often if NTP is enabled
Recommended actions
No action is required.
34
Info.
Controller has been restored to factory defaults.
Recommended actions
For an FC controller, restart it to make the default loop ID take effect.
37
Info.
Vdisk reconstruction has started. When complete, event 18 is logged.
Recommended actions
No action is required.
39
Warning
The sensors monitored a temperature or voltage in the warning range.
Recommended actions
Check that the storage system's fans are running.
Check that the ambient temperature is not too warm. The enclosure operating range is 5–40 C
(41 F–104 F).
Check that there is a module or blank plate in every module slot in the enclosure.
If none of the above explanations apply, replace the controller module that reported the error.
When the problem is fixed, event 47 is logged.
HP P2000 G3 MSA System Event Descriptions Reference Guide
13

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents