5.10 Tank temperature

Parameters indicated with an ID no. like "1x607" mean a universal
parameter.
x stands for circuit / parameter group.
MENU > Settings > Tank temperature
Flow T adapt time (Flow temperature, adaptation time)
Circuit
All
Set the adaptation time (in seconds) for the desired temperature in the
primary circuit, based on the desired charging temperature.
The ECL Comfort controller gradually increases the desired flow temperature
in the primary circuit in order to maintain the desired charging temperature.
* See Appendix "Parameter ID overview"
OFF:
The desired flow temperature in the primary circuit is
not adapted to the desired charging temperature.
Low
The adaptation is quick.
value:
High
The adaptation is slow.
value:
MENU > Settings > Tank temperature
Max. charge T (maximum heating / charging temperature)
Circuit
All
Set the max. heating / charging temperature for the DHW.
Value:
Set the temperature.
* See Appendix "Parameter ID overview"
Danfoss District Energy
ECL Comfort 210 / 310, application A247 / A347
1x068
Setting range
Factory setting
*
1x152
Setting range
Factory setting
*
The desired heating / charging temperature cannot be higher than the
set temperature in 'Max. charge T' .
*
NOTE:
The desired DHW temperature will be reduced if "Max. charge T" is
lower than (Desired DHW temp. + Charge difference).
*
Example:
Desired DHW temp. =
Charge difference =
Max. charge T =
Result:
Desired DHW temp. will be reduced to 45 °C.
VI.LG.S3.02
50 °C
10 K
55 °C
DEN-SMT/DK
105