Operating Guide
MENU > Settings > Return limit
Limit (return temp. limitation)
Circuit
All
Set the return temperature value you accept for the system.
* See Appendix "Parameter ID overview"
When the return temperature falls below or gets higher than the
set value, the controller automatically changes the desired flow /
duct temperature to obtain an acceptable return temperature. The
influence is set in 'Infl. - max.' and 'Infl. - min.'.
MENU > Settings > Return limit
High T out X1 (return temp. limitation, high limit, X-axis)
Circuit
All
Set the outdoor temperature value for the low return temperature limitation.
* See Appendix "Parameter ID overview"
The corresponding Y coordinate is set in 'Low limit Y1'.
MENU > Settings > Return limit
Low limit Y1 (return temp. limitation, low limit, Y-axis)
Circuit
All
Set the return temperature limitation referring to the outdoor temperature
value set in 'High T out X1'.
* See Appendix "Parameter ID overview"
The corresponding X coordinate is set in 'High T out X1'.
MENU > Settings > Return limit
Low T out X2 (return temp. limitation, low limit, X-axis)
Circuit
All
Set the outdoor temperature value for the high return temperature
limitation.
* See Appendix "Parameter ID overview"
The corresponding Y coordinate is set in 'High limit Y2'.
Danfoss District Energy
ECL Comfort 210 / 310, application A247 / A347
1x030
Setting range
Factory setting
*
1x031
Factory setting
Setting range
*
1x032
Setting range
Factory setting
*
1x033
Setting range
Factory setting
*
*
*
*
*
VI.LG.S3.02
DEN-SMT/DK
69