Danfoss ECL Comfort 210 Operating Manual page 153

Hide thumbs Also See for ECL Comfort 210:
Table of Contents

Advertisement

Operating Guide
ID
Parameter Name
11115
Units
11116
High limit Y2
11117
Low limit Y1
11118
Low T out X2
11119
High T out X1
11141
Ext. input
-||-
-||-
11142
Ext. mode
11147
Upper difference
11148
Lower difference
11149
Delay
11150
Lowest temp.
11174
Motor pr.
11177
Temp. min.
11178
Temp. max.
11179
Summer, cut-out
11182
Infl. - max.
-||-
11183
Infl. - min.
11184
Xp
11185
Tn
11186
M run
11187
Nz
11189
Min. act. time
11392
Sum. start, month
11393
Sum. start, day
11395
Summer, filter
Danfoss District Energy
ECL Comfort 210 / 310, application A247 / A347
A247.x
A347.x
Setting range
1, 2, 3
1, 2, 3
ml, l/h ; l, l/h
; ml, m3/h ;
l, m3/h ; Wh,
kW ; kWh, kW
; kWh, MW ;
MWh, MW ;
MWh, GW ;
GWh, GW
1, 2, 3
1, 2, 3
0.0 ... 999.9
1, 2, 3
1, 2, 3
0.0 ... 999.9
1, 2, 3
1, 2, 3
-60 ... 20
1, 2, 3
1, 2, 3
-60 ... 20
1
OFF ; S1 ; S2 ;
S3 ; S4 ; S5 ; S6
; S7 ; S8
2, 3
OFF ; S1 ; S2 ;
S3 ; S4 ; S5 ; S6
; S7 ; S8 ; S9 ;
S10 ; S11 ; S12 ;
S13 ; S14 ; S15
; S16
1, 2, 3
OFF ; S1 ; S2 ;
S3 ; S4 ; S5 ; S6
; S7 ; S8 ; S9 ;
S10
1, 2, 3
1, 2, 3
COMFORT
; SAVING ;
FROST PR. ;
CONST. T
1, 2, 3
1, 2, 3
OFF, 1 ... 30
1, 2, 3
1, 2, 3
OFF, 1 ... 30
1, 2, 3
1, 2, 3
1 ... 99
1, 2, 3
1, 2, 3
10 ... 50
1, 2, 3
1, 2, 3
OFF, 10 ... 59
1, 2, 3
1, 2, 3
10 ... 150
1, 2, 3
1, 2, 3
10 ... 150
1, 2, 3
1, 2, 3
OFF, 1 ... 50
1, 2, 3
2
-9.9 ... 0.0
1, 3
-9.9 ... 0.0
1, 2, 3
1, 2, 3
0.0 ... 9.9
1, 2, 3
1, 2, 3
5 ... 250
1, 2, 3
1, 2, 3
1 ... 999
1, 2, 3
1, 2, 3
5 ... 250
1, 2, 3
1, 2, 3
1 ... 9
1, 2, 3
1, 2, 3
2 ... 50
1, 2, 3
1, 2, 3
1 ... 12
1, 2, 3
1, 2, 3
1 ... 31
1, 2, 3
1, 2, 3
OFF, 1 ... 300
Factory
ml, l/h
999.9
999.9
-15
15
OFF
OFF
OFF
COMFORT
OFF
OFF
10
30
OFF
10
90
20
-4.0
0.0
0.0
120
50
60
3
10
5
20
250
VI.LG.S3.02
Unit
Own settings
°C
°C
K
K
Min
°C
Min
°C
°C
°C
K
Sec
Sec
K
DEN-SMT/DK
153

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ecl comfort 310A247A347

Table of Contents