Danfoss ECL Comfort 210 Operating Manual page 106

Hide thumbs Also See for ECL Comfort 210:
Table of Contents

Advertisement

Operating Guide
MENU > Settings > Tank temperature
Charge difference
Circuit
All
Set the number of degrees above the desired DHW temperature that will
result in the DHW heating (charging) temperature.
* See Appendix "Parameter ID overview"
Value: Number of degrees to be added to the desired DHW
temperature to obtain the DHW heating (charging)
temperature.
106
DEN-SMT/DK
ECL Comfort 210 / 310, application A247 / A347
1x193
Setting range
Factory setting
*
*
=
X
Time
# 1 # =
Charging difference (ID 1x193)
# 2 # =
Desired DHW temperature
# 3 # =
Start difference (ID 1x195)
# 4 # =
Actual DHW temperature
# 5# =
DHW heating / charging activity
The desired DHW temperature is related to the tank temperature
sensor.
If two tank temperature sensors are installed, the relation is to the
upper tank temperature sensor.