Operating Guide
Advice for settings:
Factory settings in the subtypes will run the most application
examples. Some of the application examples need change of
dedicated settings.
See the documentation for applications and subtypes, delivered
with the application key.
A247.1, ex. a
A347.1, ex. a
DHW circulation pipe can be connected to the DHW tank at 'A'
for internal circulation or to the heat-exchanger at 'B' for external
circulation.
Issue:
DHW circuit (2):
Internal DHW circulation
DHW circuit (2):
External DHW circulation
A247.1, ex. b
A347.1, ex. b
No special settings required.
A247.1, ex. c
A347.1, ex. c
Circuit 2 must be able to receive the heat demand from circuit 1.
Issue:
Heating circuit (1):
Heat demand
DHW circuit (2):
Heat demand
* This value is added to the heat demand value from circuit 1.
16
DEN-SMT/DK
ECL Comfort 210 / 310, application A247 / A347
Navigation:
MENU \ Settings \ Application: 'Cont. T control'
MENU \ Settings \ Application: 'Cont. T control'
Navigation:
MENU \ Settings \ Application: 'Demand offset'
MENU \ Settings \ Application: 'Demand offset'
ID no.:
12054
12054
ID no.:
11017
12017
VI.LG.S3.02
Recommended
setting:
OFF
ON
Recommended
setting:
OFF
3 K*
Danfoss District Energy