Operating Guide
MENU > Settings > Application
Demand offset
Circuit
All
The desired flow temperature in heating circuit 1 or DHW-circuit 2 can be
influenced by the demand for a desired flow temperature from another
controller (slave) or another circuit.
* See Appendix "Parameter ID overview"
OFF:
The desired flow temperature in circuit 1 or circuit 2 is
not influenced by the demand of any other controller
(slave or circuit 2).
Value: The desired flow temperature is increased by the set
value in 'Demand offset' , if the demand of the slave /
circuit 1 or circuit 2 is higher.
92
DEN-SMT/DK
ECL Comfort 210 / 310, application A247 / A347
1x017
Factory setting
Setting range
*
Heating application
*
=
X
Time
=
Y
Desired flow temperatures
=
# 1 #
Demand offset
=
# 2 #
Desired flow temperature, master
=
# 3 #
Desired flow temperature, slave
'Demand offset' with a value is to be used in the Master controller only.
If both circuits are set with a value in "Demand offset" the functionality
is disabled.
The function of 'Demand offset' can compensate for heat losses
between master and slave controlled systems.
When setting "Demand offset" to a value, the return temperature
limitation will react according to the highest limitation value (Heating
/ DHW).
VI.LG.S3.02
Danfoss District Energy