Danfoss ECL Comfort 210 Operating Manual page 65

Hide thumbs Also See for ECL Comfort 210:
Table of Contents

Advertisement

Operating Guide
MENU > Settings > Duct T limit
MENU > Settings > Room limit
Infl. - max. (room / duct temp. limitation, max.)
Circuit
All
Determines how much the desired flow / duct temperature will be influenced
(decreased) if the actual room / duct temperature is higher than the desired
room / duct temperature (P control).
* See Appendix "Parameter ID overview"
0.0:
No influence
-2.0:
Minor influence
-5.0:
Medium influence
-9.9:
Maximum influence
MENU > Settings > Duct T limit
MENU > Settings > Room limit
Infl. - min. (room / duct temp. limitation, min.)
Circuit
All
Determines how much the desired flow / duct temperature will be influenced
(increased) if the actual room / duct temperature is lower than the desired
room / duct temperature (P control).
* See Appendix "Parameter ID overview"
9.9:
Maximum influence
5.0:
Medium influence
2.0:
Minor influence
0.0:
No influence
Danfoss District Energy
ECL Comfort 210 / 310, application A247 / A347
1x182
Setting range
Factory setting
*
1x183
Factory setting
Setting range
*
Influence
*
The 'Infl. - max.' and 'Infl. - min. ' determine how much the room / duct
temperature should influence the desired flow / duct temperature.
If the 'Infl. ' factor is too high and / or the 'Adapt. time' too low, there is
a risk of unstable control.
Example 1 (application with heat curve value):
The actual room temperature is 2 degrees too high.
The 'Infl. - max. ' is set to -4.0.
The heat curve slope is 1.8 (see 'Heat curve' in 'Flow temperature').
Result:
The desired flow temperature is changed by (2 x -4.0 x 1.8)
–14.4 degrees.
Example 2 (application, no heat curve value):
The actual room temperature is 3 degrees too high.
The 'Infl. - max. ' is set to -4.0.
Result:
The desired flow temperature is changed by (3 x -4.0)
-12 degrees.
Example 1 (application with heat curve value):
The actual room temperature is 2 degrees too low.
The 'Infl. - min. ' is set to 4.0.
The heat curve slope is 1.8 (see 'Heat curve' in 'Flow temperature').
Result:
The desired flow temperature is changed by (2 x 4.0 x 1.8)
*
14.4 degrees.
Example 2 (application, no heat curve value):
The actual room temperature is 3 degrees too low.
The 'Infl. - min. ' is set to 4.0.
Result:
The desired flow temperature is changed by (3 x 4.0)
12 degrees.
VI.LG.S3.02
'Infl. - min.' (min. limitation)
Desired room / duct
temperature
Actual room / duct
temperature
'Infl. - max.' (max. limitation)
DEN-SMT/DK
65

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ecl comfort 310A247A347

Table of Contents