Danfoss ECL Comfort 210 Operating Manual page 109

Hide thumbs Also See for ECL Comfort 210:
Table of Contents

Advertisement

Operating Guide
MENU > Settings > Tank temperature
MENU > Settings > Refill tank
Start difference
Circuit
All
Set the number of degrees below the desired DHW temperature that will
start the DHW heating (charging).
* See Appendix "Parameter ID overview"
Value:
Set the number of degrees.
Danfoss District Energy
ECL Comfort 210 / 310, application A247 / A347
1x195
Setting range
Factory setting
*
*
=
X
Time
# 1 # =
Charging difference (ID 1x193)
# 2 # =
Desired DHW temperature
# 3 # =
Start difference (ID 1x195)
# 4 # =
Actual DHW temperature
# 5# =
DHW heating / charging activity
Example:
Desired DHW temp.:
Start difference:
Result:
The DHW heating starts when the temperature measured by the tank
temperature sensor (upper) is lower than 52 °C.
VI.LG.S3.02
55 °C
-3 K
DEN-SMT/DK
109