Operating Guide
MENU > Settings > Application
MENU > Settings > Tank temperature
DHW P post-run (DHW pump, post-run)
Circuit
All
Set the DHW pump post-run time (minutes). The DHW pump can continue
to be switched ON after the DHW heating procedure in order to utilize the
remaining heat in the heat exchanger / boiler.
* See Appendix "Parameter ID overview"
Value: Set the number of minutes for the post-run.
MENU > Settings > Application
MENU > Settings > Tank temperature
Char. P post-run (DHW charging pump, post-run)
Circuit
All
Set the DHW charging pump post-run time (minutes). The DHW charging
pump can continue to be switched ON after the DHW heating procedure in
order to utilize the remaining heat in the heat exchanger.
* See Appendix "Parameter ID overview"
Value: Set the number of minutes for the post-run.
MENU > Settings > Application
Max. DHW time
Circuit
All
Set the max DHW heating time (minutes). When DHW heating is active and
the set 'Max. DHW time' expires, DHW heating is deactivated.
* See Appendix "Parameter ID overview"
OFF:
If the DHW temperature is lower than the DHW charging
cut-in temperature, the DHW charging remains active
for unlimited period of time. If the DHW temperature is
higher than the DHW charging cut-in temperature, the
charging is deactivated after 35 minutes.
Value:
The DHW heating / charging is deactivated when the set
'Max. DHW time' (in minutes) expires.
94
DEN-SMT/DK
ECL Comfort 210 / 310, application A247 / A347
1x041
Setting range
Factory setting
*
1x042
Setting range
Factory setting
*
1x044
Factory setting
Setting range
*
*
*
*
VI.LG.S3.02
Danfoss District Energy