Operating Guide
MENU > Settings > Return limit
Adapt. time (adaptation time)
Circuit
All
Controls how fast the return temperature adapts to the desired return
temperature limit (Integration control).
* See Appendix "Parameter ID overview"
OFF:
The control function is not influenced by the 'Adapt.
time' .
Minor
The desired temperature is adapted quickly.
value:
Major
The desired temperature is adapted slowly.
value:
MENU > Settings > Return limit
Priority (priority for return temp. limitation)
Circuit
All
Choose whether the return temperature limitation should overrule the set
min. flow temperature 'Temp. min.' .
* See Appendix "Parameter ID overview"
OFF:
The min. flow temperature limit is not overruled.
ON:
The min. flow temperature limit is overruled.
Danfoss District Energy
ECL Comfort 210 / 310, application A247 / A347
1x037
Setting range
Factory setting
*
1x085
Setting range
Factory setting
*
The adaptation function can correct the desired flow / duct
temperature with max. 8 K.
*
If you have a DHW application:
Please also see 'Parallel operation' (ID 11043).
*
If you have a DHW application:
When dependent parallel operation is in function:
•
Desired flow temperature for the heating circuit will be minimum
limited, when "Priority for return temperature" (ID 1x085) is set
to OFF.
•
Desired flow temperature for the heating circuit will not be
minimum limited, when "Priority for return temperature"
(ID 1x085) is set to ON.