Operating Guide
MENU > Settings > Return limit
Adapt. time (adaptation time)
Circuit
All
Controls how fast the return temperature adapts to the desired return
temperature limit (Integration control).
* See Appendix "Parameter ID overview"
OFF:
The control function is not influenced by the 'Adapt.
time' .
Minor
The desired temperature is adapted quickly.
value:
Major
The desired temperature is adapted slowly.
value:
MENU > Settings > Return limit
Priority (priority for return temp. limitation)
Circuit
All
Choose whether the return temperature limitation should overrule the set
min. flow temperature 'Temp. min.' .
* See Appendix "Parameter ID overview"
OFF:
The min. flow temperature limit is not overruled.
ON:
The min. flow temperature limit is overruled.
Danfoss District Energy
ECL Comfort 210 / 310, application A247 / A347
1x037
Setting range
Factory setting
*
1x085
Setting range
Factory setting
*
The adaptation function can correct the desired flow / duct
temperature with max. 8 K.
*
If you have a DHW application:
Please also see 'Parallel operation' (ID 11043).
*
If you have a DHW application:
When dependent parallel operation is in function:
Desired flow temperature for the heating circuit will be minimum
limited, when "Priority for return temperature" (ID 1x085) is set
to OFF.
Desired flow temperature for the heating circuit will not be
minimum limited, when "Priority for return temperature"
(ID 1x085) is set to ON.
VI.LG.S3.02
DEN-SMT/DK
71