Danfoss ECL Comfort 210 Operating Manual page 75

Hide thumbs Also See for ECL Comfort 210:
Table of Contents

Advertisement

Operating Guide
MENU > Settings > Control par., fan
MENU > Settings > Control par., inlet
MENU > Settings > Control par., outlet
MENU > Settings > Flow / power limit
MENU > Settings > Refill tank
MENU > Settings > S7 (S8, S9, S10) pressure
Filter constant
Circuit
All
The value of the filter constant determines the dampening of the measured
value.
The higher the value, the more dampening.
By this, a too quick change of the measured value can be avoided.
* See Appendix "Parameter ID overview"
Minor
Lower dampening
value:
Major
Higher dampening
value:
MENU > Settings > Flow meter
MENU > Settings > Flow / power limit
Pulse
Circuit
All
Set the value of the pulses from the flow / energy meter.
* See Appendix "Parameter ID overview"
OFF:
No input.
1 ... 9999: Pulse value.
Danfoss District Energy
ECL Comfort 210 / 310, application A247 / A347
1x113
Factory setting
Setting range
*
1x114
Setting range
Factory setting
*
*
Example :
One pulse can represent a number of litres (from a flow meter)
or a number of kWh (from a energy meter).
*
Pulse based signal for flow / power, applied to input S7
For monitoring:
Frequency range is 0.01 - 200 Hz
For limitation:
Minimum frequency is recommended to be 1 Hz in order to have a
stable control. Furthermore, the pulses must appear regularly.
VI.LG.S3.02
DEN-SMT/DK
75