Danfoss ECL Comfort 210 Operating Manual page 33

Hide thumbs Also See for ECL Comfort 210:
Table of Contents

Advertisement

Operating Guide
2.5.6 Electrical connections, master / slave systems
The controller can be used as master or slave in master / slave
systems via the internal ECL 485 communication bus (2 x twisted
pair cable).
The ECL 485 communication bus is not compatible with the ECL
bus in ECL Comfort 110, 200, 300 and 301!
Terminal Description
30
Common terminal
31*
+12 V*, ECL 485 communication bus
32
B, ECL 485 communication bus
33
A, ECL 485 communication bus
* Only for ECA 30 / 31 and master / slave communication
2.5.7 Electrical connections, communication
Electrical connections, Modbus
ECL Comfort 210: Non-galvanic isolated Modbus connections
ECL Comfort 296: Non-galvanic isolated Modbus connections
ECL Comfort 310: Galvanic isolated Modbus connections
2.5.8 Electrical connections, communication
Electrical connections, M-bus
ECL Comfort 210: Not implemented
ECL Comfort 296: On board
ECL Comfort 310: On board
Danfoss District Energy
ECL Comfort 210 / 310, application A247 / A347
Type
(recomm.)
Cable 2 x
twisted pair
Total cable length: Max. 200 m (all sensors incl. internal ECL 485
communication bus).
Cable lengths of more than 200 m may cause noise sensibility (EMC).
Total cable length: Max. 200 m (all sensors incl. internal ECL 485
communication bus).
Cable lengths of more than 200 m may cause noise sensibility (EMC).
VI.LG.S3.02
DEN-SMT/DK
33

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ecl comfort 310A247A347

Table of Contents