Output Device Programming; About Output Device Programming - ADEMCO VISTA-10ES Installation And Setup Manual

Table of Contents

Advertisement

• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •

About Output Device Programming

This system supports up to four relays (devices) when a 4204 relay module is connected. The following explanations will
help you understand the programming of output devices when using 80 (this section) and 81 (SECTION 7: Zone Lists
that follows). The options used to start and stop these devices are described below, followed by the actual screen prompts
and available entries. We recommend that you first fill out the Output Relays Worksheet for Fields 80 and 81 in the
separate Programming Form prior to programming.
Relays and output devices are not recommended for life safety applications.
The letter(s) in parentheses after each function described below, such as (A) after ACTION, are those that appear in the
various summary displays of programmed data during programming.
ACTION (A)
The "ACTION" of the relay is how the relay will respond when it is activated by the "START" programming. You may
want the relay to activate momentarily, to pulse on and off continuously, or to remain activated until some other event
occurs to stop it. There are four different choices of actions:
ACTIVATE for 2 SECONDS and then reset.
ACTIVATE and remain ACTIVATED until stopped by some other event.
PULSE ON and OFF until stopped by some other event.
NOT USED when the relay is not used.
START (STT)
The "START" programming determines when and under what conditions the relay will be activated. The following
START options are available :
1.
EVENT (EV) is the condition (alarm, fault, trouble) that must occur to a zone or group of zones (zone list) in
order to activate the relay. These conditions apply only when a zone list is used. The different choices for
"EVENT" are listed below and in the "Programming Output Devices" paragraph that follows.
ALARM Relay action begins upon any alarm in an assigned zone in the zone list.
FAULT Relay action begins upon any opening or short in an assigned zone in the zone list.
TROUBLE Relay action begins upon any trouble condition in an assigned zone in the zone list.
NOT USED Relay action is not dependent upon one of the above events.
2.
ZONE LIST (ZL) is a group of zones to which the "EVENT" applies in order to activate a particular relay. Note
that there are a total of 3 zone lists that can be programmed in field
(Alarm, Fault or Trouble) occurs in any zone in the selected "Start" ZONE LIST (1, 2, or 3), activation of the
selected relay will START.
3.
ZONE TYPE/SYSTEM OPERATION (ZT). If a System Operation, such as "DISARMING" or "ANY FIRE
ALARM," is to activate the relay, the appropriate choice would also be entered under the "ZONE TYPE" option.
"ZONE TYPE" is used independently of the "EVENT/ZONE LIST" combination.
If a specific "ZONE TYPE" is chosen, any zone of that response type going into alarm, trouble, or fault will cause
the relay to activate as selected in "ACTION." If the same "ZONE TYPE" is also chosen for the STOP
programming, any zone of that type that restores will de-activate the relay.
If a "SYSTEM OPERATION" is chosen (e.g., End of Exit Time), that operation will cause the relay to activate as
selected in "ACTION." The different choices for "ZONE TYPE" and "SYSTEM OPERATION" are listed in the
"Programming Output Devices" paragraph later in this section, and in the Programming Form.

Output Device Programming

S E C T I O N
( 80 Menu Mode)
81 mode; when the selected EVENT
6
6–1

Advertisement

Table of Contents
loading

Table of Contents