5-4. M-NET system setting example

(1) Setting example for connecting one or more AE-50 controllers
AE-200
(Main system controller)
LAN1 IP: 192.168.1.1
[000]
LAN
Switching
HUB
● When a Sub system controller (i.e., ON/OFF remote controller) is connected, disconnect the M-NET power jumper (CN21)
from AE-200 or AE-50 to supply power from the power supply unit (PAC-SC51KUA) or the outdoor unit (TB7).
(2) Setting example for connecting multiple M-NET system controllers
AE-200
(Main system controller)
[000]
Power supply unit
(PAC-SC51KUA)
ON/OFF remote controller
(Sub system controller)
[201]
● Make the initial settings such as group settings and interlock settings. Refer to the AE-200 Instruction Book and the Instruction
Book (Web Browser for Initial Settings) for details.
● Designate a system controller within the system as the only controller from which the operation prohibit setting can be made.
● Disconnect the M-NET power jumper (CN21) from the AE-200.
WT07137X01
M-NET
ON/OFF remote controller
(Sub system controller)
[201]
AE-50_1
LAN
LAN1 IP: 192.168.1.211
[000]
AE-50_2
LAN1 IP: 192.168.1.212
[000]
2 M-NET adapters
(adapter address 21 and 22)
AE-50_3
LAN1 IP: 192.168.1.213
[000]
M-NET
50 indoor units
Groups 1–20
19
Power supply unit
(PAC-SC51KUA)
M-NET
ON/OFF remote controller
(Sub system controller)
[201]
M-NET
M-NET
Numbers in parentheses indicate address
numbers.
50 indoor units
50 indoor units
20 indoor units
Groups 1–20
Mr. Slim outdoor units
Groups 21 and 22
50 indoor units
Groups 1–20