6-5. Installation space

Leave a space around the AE-200/AE-50 as shown in the figure below.
30 (1-3/16)
284 (11-5/32)
40 (1-37/64)
Note
● When installing two or more AE-200/AE-50 controllers side-by-side, leave a space of at least 30 mm (1-3/16 in) between
them.
● When installing two or more AE-200/AE-50 controllers vertically, leave a space of at least 40 mm (1-37/64 in) between them.
● For the installation space for installation method 4, refer to the separately-sold mounting kit's Installation Manual .

6-6. Installation procedures

Note
● Connect the necessary cables and wires before installing AE-200/AE-50, referring to chapters 7 and 10.
Important
● When routing the cable from above, let the cable hang loose behind the controller as shown in the figure below to prevent
water from running down the cable into the connectors.
Good example
6-6-1. Cutting an installation hole and screw holes in the wall (Methods 1 and 2)
Cut an installation hole (169 × 252 mm (6-21/32 × 9-59/64 in)) and screw holes in the wall as shown in the figure
below.
252 (9-59/64)
217 (8-35/64)
WT07137X01
Unit: mm (in)
Bad example
Unit: mm (in)
ø6 (ø15/64)