System Configuration Example; System With Connection To A Pac-Yg50Eca Expansion Controller; Using Multiple System Controllers; To Control A Mr. Slim - Mitsubishi Electric AG-150A-A Installation Manual

Air-conditioner control system
Hide thumbs Also See for AG-150A-A:
Table of Contents

Advertisement

10 System Configuration Example

1. System with connection to a PAC-YG50ECA Expansion controller

*1
AG-150A
192.168.1.1
24VDC
Power supply unit for transmission line
(Model name: PAC-SC51KUA)
*1 M-NET address settings
are not required.

2. Using multiple system controllers

• Make the initial settings (e.g., group settings and interlock settings) from the AG-150A, which is a main system controller, or
from the Initial Settings Web.
• Designate a single system controller in a given system from which operation prohibition signal can be sent.

3. To control a Mr. Slim

* An M-NET adapter (sold separately) is required to
connect and control the Mr. Slim model of units to the
M-NET.

4. To control a K control model

* Set AG-150A address to "000" when a K transmission converter is
connected. Always set to the main system controller when the
address is "000".
* Set the address of the K-control indoor units to a larger number
than those of the M-transmission models of indoor units.
* When using a group setting for the K control model, set only the
indoor unit that belongs to that group.
* Set the minimum indoor unit address in the group for the K control
model group number.
LAN
LAN
Switching
HUB
AG-150A
(Main system controller)
ON/OFF remote
controller etc.
(Sub system controller)
Expansion controller
M-NET
(PAC-YG50ECA)
192.168.1.211
000
Expansion controller
M-NET
(PAC-YG50ECA)
192.168.1.212
000
Expansion controller
M-NET
(PAC-YG50ECA)
192.168.1.213
000
000
24VDC
201
Power supply unit for transmission line (Model name: PAC-SC51KUA)
AG-150A
000
(Main system controller)
Power supply unit for transmission line (Model name: PAC-SC51KUA)
AG-150A
(Main system controller)
- 25 -
Indoor units: 50 units
ON/OFF remote
controller etc.
201
M-NET adapter
Indoor unit: 20 units
Indoor unit address 01 ~ 20
Group 1 ~ Group 20
Mr. Slim outdoor unit (M-NET
adapter)
M-NET adapter: 2 units
M-NET adapter address 21 ~ 22
Group 21, 22
Indoor unit (M-NET): 20 units
Indoor unit address 01 ~ 20
Group 1 ~ Group 20
Indoor unit (K-control): 30 units
Indoor unit address 21 ~50
Group 21 ~ Group 50
K transmission converter (Model name: PAC-SC25KAA)
Indoor units: 50 units
Group 1 ~ Group 20
M-NET adapter
Indoor unit address 01 ~ 20
Group 1 ~ Group 20
Mr. Slim outdoor unit (M-NET
adapter)
M-NET adapter: 2 units
M-NET adapter address 21 ~ 22
Group 21, 22
20 indoor units
Indoor unit address 01~20
M-NET
Group 1 to Group 20
20 indoor units (for control)
Indoor unit address 21~40
Group 21 to Group 40
PAC-SC25KAA
K transmission converter
24VDC
PAC-SC51KUA
Power supply unit
: IP address
: M-NET address