4. Specifications

4-1. Product specifications

Rated input
Power supply
Fuse
M-NET power feeding capability
Temperature
Ambient
conditions
Humidity
Dimensions (W × H × D)
Weight
Installation conditions
WT07137X01
Item
Operating temperature
range
Storage temperature
range
100–240 VAC ± 10%; 0.21–0.12 A 50/60 Hz Single-phase
250 VAC 6.3 A Time-Lag type (IEC 60127-2S.S.5)
No specifications
* Only an MN converter can be connected.
0°C – +40°C (+32°F – +104°F)
-20°C – +60°C (-4°F – +140°F)
30%–90% RH (Non-condensing)
284 × 200 × 65 mm
(11-5/32 × 7-55/64 × 2 17/32 in)
* When installed, AE-200/AE-50 will protrude 25.0 mm (31/32 in) from the
wall or the metal control box.
2.3 kg (5-5/64 lbs)
Indoor only
* To be used in a business office or similar environment