4.13 SETTING FOR COMMISSION OF THE ATTACK DPX LAMBDA

The device can be commissioned, when the minimum requirements for the testing operation or
heating are fulfilled (see the chapter 1.2). Then it is necessary to make the following settings.
Settings by using the code of the service technician
The button „←" enables to enter into the menu of Options, where the submenu „settings" can be
changed by the „+" and „–". The button „←" is used to confirm the selection.
Exit from the submenu comes automatically after selecting the „supply valve" by the button „←".
Then is the display automatically switched into the operating mode. If no button is pressed
during 1 minute, the display is automatically switched to the operating mode.
Settings:
Menu
Information
Test of device
Safety test
Setting
Submenu
Entering the code
---
01 :Language
German
DE
English
GB
Spanish
ES
Italian
IT
French
FR
Swedish
SE
Polish
PL
Slovak
SK
Czech
CZ
Dutch
NL
Danish
DK
Hungarian
HU
Slovenian
SI
02: Boiler setting
°C
85
03: TAG setting
°C
180
04: O
setting
2
%
6,0
05 : TAD start
K
60
Indication
Set the code by the „+" button. The random
number is displayed on the left side. Enter the
code and confirm by the button „←". The code
for service technician is available by producer.
Function: Setting the national language
Function: Set the temperature in the boiler
Producer: 85 °C
Range for setting: 75–85 °C
Function: Setting the flue gas temperature
(nominal boiler output 180 °C).
Producer: 180 °C
Range for setting: 110–240 °C
Note: TAG = flue gas temperature
Function: Setting the O
Producer: 6,0 %
Range for setting: 4,0–8,0 %
Function: To get the sufficient output of
heating before closing the feeding door
Producer: 60K
Range for setting: 25K d – 125K
Note: TAD = temperature difference.
Difference between the flue gas temperature
and the temperature in the boiler.
value for burning 6 %