Attack Dpx Lambda - ATTACK DPX15 Instructions For Use Manual

Dpx wood gasifying boiler standard / profi / lambda
Hide thumbs Also See for DPX15:
Table of Contents

Advertisement

1.5.2 ATTACK DPX LAMBDA

Indicator light 1:
automatically stops after the fuel burns down or when the boiler was manually
stopped by the button „–" (6).
Indicator light 2:
o
incorrectly measured values of the flue gas temperature
o
see the chapters Errors and alarms
Indicator light 3:
o
STB started – Reset (error, message (3) displayed)
o
incorrectly measured values of the boiler temperature (error, message (3) displayed)
o
too high flue gas temperature (alarm, message (3) displayed)
o
overheating – do not open! (boiler temperature over 90 °C, display 3 flickers )
o
see the chapter Errors and alarms
Display 4:
Displays the operating data for different settings by errors. If the boiler is stopped
and no fault is displayed, the display illumination is turned off after 15 minutes.
Button 5 (+):
The display illumination is turned on after pressing the button for the first time.
The boiler is started after the button is pressed again – then it is possible to heat it
up or to refill the fuel. Also other settings can be done by this button (see the
Button 7 below).
Button 6 (–):
Serves to stop the boiler. This function is used only for an emergency stop, e.g. if
there is no water in the heating system or is the sensor for overheating is not
working. Also other settings can be done by this button (see the Button 7 below).
Button 7 (←): The display illumination is turned on after pressing the button for the first time.
Press the button again to get into the „Options". Use the buttons „+" (5) or „–" (6)
to get to the various data or to make settings.
! There are various functions of the buttons 5 and 6.
Button 8:
Reset the button of the safety thermostat (STB)
If the STB had been started because of the excessive boiler temperature (≥95˚C)
and the boiler temperature decreased to 85 °C, you can reset the STB by
removing the cover (8) and pressing the button underneath (8). The error is
automatically removed. If the error occurs again, inform the technician.
Reasons: small outtake of heat, power shortage, circuit pump – faulty mixing
valve. To decrease the temperature to 85 °C, the regulator starts the supply
pump.
If the flue gas fan does not work, do not open the boiler door!
10
Lights, when the boiler was started by the button „+" (5)
Lights in case of the following faults:
Lights or flickers in the case of error or alarm:
Key:
1. – Green indicator light
2. – Yellow indicator light
3. – Red indicator light
4. – Display
5. – Button „+"
6. – Button „–„
7. – Button „←"
8. – Reset of the safety
thermostat