SMA Solar Technology America LLC
Display no.
Description
E853
Sunny Island Charger #3 detected
E854
Sunny Island Charger #4 detected
E901
SOC recalibration started
E902
SOC recalibration stopped
E903
Derating started
E904
Derating stopped
E905
Preventive self-disconnection to protect the battery from deep discharge
20.7 Failure Categories
The Sunny Island distinguishes between five different levels of errors, each requiring different user
interaction:
Level
Designation
1
Warning
2
Malfunction 1 Malfunction
3
Malfunction 2 Malfunction
4
Error
5
Device defect
20.8 Warnings and Error Messages
The meanings of the warnings and errors displayed by the Sunny Island are described in the following
table:
Operating Manual
Display
Meaning
Warning
Warning, device continues to run. There is an explicit
information on the Home Screen that a warning was
recorded.
Failure that can only be detected during operation.
Device switches off. Device can be restarted
immediately (autostart).
Failure that can also be detected in standby mode.
Device switches off. The device can only be restarted
(autostart) once the system detects that the
malfunction has ended.
Failure
Device error, device switches off. User interaction
required (troubleshooting, confirmation, manual
restart)
Defect
Device is defect. Device switches off and does not
switch on again. Permanent operation inhibition.
Device must be replaced.
20 Troubleshooting