SMA SUNNY ISLAND 4548-US Operating Manual page 170

Off-grid inverter
Hide thumbs Also See for SUNNY ISLAND 4548-US:
Table of Contents

Advertisement

19  Parameter Lists
No. Name
11
BatTmpCps
12
AutoEquChrgEn
a
#223 Battery Protection
No. Name
01
BatPro1TmStr
02
BatPro1TmStp
03
BatPro2TmStr
04
BatPro2TmStp
05
BatPro1Soc
06
BatPro2Soc
07
BatPro3Soc
170
SI4548-6048-US-BE-en-21
Description
Value
Battery
0 mV/C° to
temperature
10 mV /°C
compensation
Automatic
Disable
equalization
Enable
charge
Description
Starting time of the
battery-preservation
mode (level 1)
End time of the
battery-preservation
mode (level 1)
Starting time of the
battery-preservation
mode (level 2)
End time of the
battery-preservation
mode (level 2)
State of charge for
battery-preservation
mode, level 1
State of charge for
battery-preservation
mode, level 2
State of charge for
battery-preservation
mode, level 3
SMA Solar Technology America LLC
Explanation
VRLA
FLA
NiCd
Disable
Enable
Value
Default value
22:00:00
06:00:00
17:00:00
09:00:00
0% to 70%
20%
0% to 70%
15%
0% to 70%
10%
Default
value
4.0 mV/
°C
4.0 mV/
°C
0 mV/
°C
Enable
Operating Manual

Advertisement

Table of Contents

Troubleshooting

loading

This manual is also suitable for:

Sunny island 6048-usSunny island 4548-us-10

Table of Contents